• Air Conditioning

Main Office Areas Four pipe fan coil
Listed Areas Two pipe fan coil, with electric heating

• Cooling Capacity
Total 3.0MW undiversified

• Internal Acoustic Criteria
Offices NR38
Toilets NR40

• External Design Criteria
Summer 28C db 20C wb
Winter -4C db 100%rh

• Design Occupancy
10m2 per person

• Lighting
Offices 350-450 lux

• Lifts
Principal Lifts
Passenger (ground to seventh) Bank 1-Four 16 person
Passenger (ground to seventh) Bank 2-Four 13 person
Average Waiting Time Less than 30 seconds

Ancillary Lifts
Passenger (seventh to ninth) One 8 person
MIP (street to Ground) One 8 person
Fire fighting (North core) One 8 person
Fire Fighting (South Core) One 16 person
Goods (Basement 2 to Seventh) One 26 person (1,800kg)

 


• Slab to slab height

Between 3.3m and 4.7m

• Planning Grid
Existing Imperial (5790mm x 3090mm)

• Floor Loading
Imposed 2.5 kN/m2 + 1 kN/m2 partition load

• Floor to ceiling height
Generally 2700mm

• Raised floor void
100mm clear (overall)

• Population Densities
Office 10m2 per person
Fire 10m2 per person
Lifts 10m2 per person
Mechanical
systems 10m2 per person

• Electrical
Transformer 1no. twin 800KVA 1 no. Twin 1000KVA
Switchpanels 2no. 800Amp, 2no. 1600Amp
Office Lighting T5 Cat2 luminaires

• Small Power
Small Power 15w per m2
Lighting 12w per m2

• Standby Power
Landlords 150 KVA standby generator
Tenants space allocated for generator(s)